Categories
EMHB 2 Ex
EMHB 2 Ex lighting fixture - zone 2 21,22
The EMHB 2 Ex luminaire is designed to illuminate, among others:
- industrial halls and spaces classified in zones 2, 21 and 22 of the risk of explosion of dust, gases, vapours and mists of flammable liquids,
- auxiliary rooms with high dust levels and the possibility of water splashes, i.e. boiler rooms, water supply systems, baths, garages, shelters, open and closed warehouses,
- process lines of the following industries: chemical, oil, petrochemical, gas, wood, processing of loose mining, construction and food materials
- rooms with elevated temperatures
Technical parameters | ||
Parameter name | Value (unit) | |
Supply voltage | 90-305 VAC 140-250 VDC 50-60/0Hz | |
Power | 40-270W ±5% | |
Power factor | PF ≥ 0.95 * * | |
ATEX marking | II 3G Ex ec op is IIC T5..T4 Gc | |
IECEx marking | Ex ec op is IIC T5...T4 Gc; Ex tb op is IIIC T80°C...T115°C Db | |
Standards | PN-EN 60079-0:2018, PN-EN 60079-7:2016, | |
Light source | ultra bright LEDs | |
Color temperature | 4000K ±10% | |
Luminous flux | 155lm/W ±10% | |
Protection class | AND | |
Protection level | IP66/67 *** | IK 10 |
Permissible temperature | according to the table below | |
Mass | 6.8kg | |
External dimensions | Ø380x150mm |
* According to the table of types of execution
** At a voltage of 230VAC and a power of 160W
*** If a cable entry with a lower IP is used, the protection class of the entire luminaire is reduced - see instructions, point 8.2.