Categories
DESCRIPTION
EM410 module controls two independent relay outputs and monitors the status of six binary inputs with line continuity monitoring. Information about the status of inputs is sent via available internal interfaces to the application module, which uses the same interfaces to control the operation of output systems. The application module in the ELSAFE-14 system is the EM440 module. Binary outputs ensure the safety integrity level of SIL 2 with program control. The inputs are dedicated to cooperation with the Terminal Resistor Group - ZRK).
FEATURES/TECHNICAL SPECIFICATION
General parameters
Parameter name | Value (unit) |
Supply voltage | +12V to +15V DC |
Maximum current consumption | 210mA |
ATEX marking | |
EC type examination certificate number | TEST 15 ATEX 0009X |
Ambient temperature range | -20 ABOUT C ÷ +40 ABOUT C |
Degree of protection according to PN-EN 60529:2003 | IP20 |
Number of binary inputs with line continuity control | 6 |
Number of NO relay outputs (make contacts) | 2 |
Maximum contact current | 2 A |
Maximum contact voltage | 60V |
Maximum contact switching power | 60 W |
Maximum diameter of Combicon connector cable | 2.5mm 2 |
Module dimensions | 114.5 x 99 x (22.5 + 8) mm |
Mass | 220g |
General parameters
Parameter name | Value (unit) |
Functional safety parameters (according to PN-EN 62061) | |
SIL Level / Safety Performance Level | SIL CL 2 / PLd |
Probability of PFHD hardware damage | 1.21E-07 |
Safe Failure Factor SFF | 98% |
DC diagnostic coverage | 95% |
NOTE: Output circuits connected to connector Z3 retain the “ia” protection level when the module is powered from a power supply with a lower protection level.
DOCUMENTATION